Commercial Kitchen Make Up Air Units
Need commercial kitchen make up air units for a new restaurant, or a replacement on an existing hood? We handle both.
We match the unit to your hood exhaust CFM, heating or cooling, fuel, and roof or wall mount.
We select the make-up air unit and its exhaust fan, quote both, and return a submittal-ready selection.
Our offices are in Houston and Dallas-Fort Worth, serving Texas and the Gulf Coast, and we ship nationwide.
Not sure which make-up air unit fits your kitchen hood?
We match the unit to your exhaust CFM and climate.
Kitchen Make-Up Air Unit Types
Five unit types supply make-up air to a kitchen hood. Choose by climate, fuel and roof space.
| Unit type | Best for | Falls short when |
|---|---|---|
| Untempered supply fan | Small hoods with spare air-conditioning capacity | Summers are humid or winters are cold |
| Direct gas-fired heated unit | Large kitchens, up to 21,000 CFM | Summer cooling is needed |
| Indirect gas-fired heated unit | Supply air kept free of combustion products | The roof cannot take a flue |
| Electric heated unit | Sites with no gas service | Airflow is high, since 3,000 CFM at a 30°F rise needs 28.5 kW |
| DX cooled unit | Humid Gulf Coast summers | No room for a condensing section |
Common Questions
How much make-up air does a commercial kitchen hood need?
A commercial kitchen hood needs make-up air for most of its exhaust. A tempered make-up air unit usually supplies 70 to 90% of the exhausted air, per Accurex. The building's air conditioning supplies the rest, which keeps the kitchen slightly negative to the dining room.
Can I use evaporative cooling for kitchen make-up air in Houston?
Evaporative cooling is a poor fit for kitchen make-up air in Houston. An evaporative cooler cools by adding water to the air. Houston's wet bulb stays above 73°F for about 2,533 hours a year, per NOAA, and in those hours the cooler adds moisture with little cooling. DX cooling is the better choice.
Direct-fired or indirect-fired make-up air for a restaurant kitchen?
Pick direct-fired make-up air for a restaurant kitchen unless combustion products must stay out of the supply air. A direct-fired burner heats the outdoor airstream directly, with no flue, in units up to 21,000 CFM. An indirect-fired unit heats air through a heat exchanger and vents combustion products through a flue.
Can a make-up air unit be added to an existing kitchen hood?
A make-up air unit can be added to an existing kitchen hood, sized to the exhaust fan's measured airflow rather than the hood label. For example, an exhaust fan measured at 3,000 CFM pairs with a unit supplying about 2,100 to 2,700 CFM, wired to start with that fan.
Cooled Make-Up Air for Houston and Gulf Coast Kitchens
Houston kitchen make-up air needs cooling and drying as well as winter heat. At the 0.4% summer design condition, outdoor air at Houston Bush Intercontinental carries 146 grains of moisture per pound of dry air, per NOAA.
Indoor air at 75°F and 50% relative humidity holds about 65 grains. An untempered unit brings in over twice that moisture, which the building’s air conditioning must remove.
A DX cooling coil in the unit cools outdoor air below its dew point and drains the condensate. A direct gas-fired heater on the same unit covers winter, when Houston’s design temperature is 27°F.
Make-Up Air Matched to the Hood Exhaust Fan
We size the make-up air unit from the hood exhaust fan’s airflow and quote both as one commercial kitchen ventilation package.
NFPA 96 Section 8.3.1 limits negative pressure in the cooking area to 0.02 inches of water column. Houston’s mechanical code, based on the 2021 Uniform Mechanical Code, has applied since January 2, 2024.
An interlock starts the make-up air unit with the exhaust fan. With demand-controlled exhaust, a variable-speed supply motor lets airflow follow the exhaust.
Need cooled make-up air for a Gulf Coast kitchen?
We pair the unit with your hood exhaust fan.
Related Kitchen Ventilation Equipment
- Centrifugal fansExhaust and supply fans for hoods
- Mixed flow fansInline fans where duct space is limited
- Backward inclined blower fansHigh static pressure, long duct runs
- Forward curved blowersBlowers for packaged supply units
- Inline electric duct heatersElectric heat for supply air in the duct
- Gas-fired duct furnacesGas heat for supply air in the duct
- Fixed louversOutdoor air intakes for wall-mounted units
- Makeup air units for cruise shipsMake-up air for galleys at sea
- Hospital ventilation equipmentHospital kitchens and clinical areas